Fire-resistant cables are subject to specific requirements depending on their operating conditions. They cover a broad range of AC rated voltages, including the V series (600/1000V), K series (450/750V), and B series (450/750V). The maximum long-term operating temperature of a cable varies according to its insulation material:
Cables with flame-retardant polyvinyl chloride (PVC) or cross-linked polyethylene (XLPE) insulation can withstand temperatures of 70°C–105°C and 90°C, respectively.
Fluoroplastic-insulated cables are rated for 220°C or 260°C; other variants - rated for 90°C or 125°C - may be paired with a 105°C flame-retardant PVC sheath.
Cables with low-halogen, low-smoke, flame-retardant PVC insulation and sheathing are rated for 70°C, while those using halogen-free, low-smoke, flame-retardant polyolefin materials are rated for 90°C or 125°C.
In extremely low ambient temperatures, the cables must meet the following criteria: for those with flame-retardant PVC insulation and sheathing, the minimum temperature is -40°C for fixed installations and -15°C for non-fixed installations; for cables with fluoroplastic insulation and sheathing, the corresponding limits are -60°C and -20°C, respectively.
During installation, the cable temperature must not fall below 0°C. These cables possess fire-resistant properties in compliance with IEC 331 and GB 12666.6 standards. They are designed to withstand exposure to flames (at temperatures ranging from 750°C to 1000°C) for 3 hours; following a 21-hour cooling period, they must remain capable of carrying their rated voltage and current (e.g., 3A). These cables are classified into Category A and Category B.
There are also specific requirements for the bending radius during installation: for non-armored or braided-shielded cables, the bending radius must be at least 6 times the outer diameter; for steel-tape armored cables, it must exceed 12 times the outer diameter; and for cables with fluoroplastic insulation and sheathing, it must be at least 8 times the outer diameter.