Given the specific characteristics of fire-resistant cables, designers should consider the following points when selecting and specifying them:
(1) When fire-resistant cables are used in areas with a high density of cables-such as cable tunnels or cable trenches-or in locations near flammable materials (e.g., oil pipelines or oil storage facilities), Class A fire-resistant cables should be the primary choice. In other scenarios where the number of cables is limited, Class B fire-resistant cables may be used.


(2) Fire-resistant cables are primarily used for emergency power supply circuits, which must remain operational during a fire. Because ambient temperatures rise sharply during a fire, the cross-sectional area of ​​fire-resistant cables should be increased by at least one standard size for long-run circuits with strict allowable voltage drop limits; this ensures the circuit maintains its required power transmission capacity and minimizes voltage drop.


(3) Fire-resistant cables should not be used as high-temperature-resistant cables.


(4) To reduce the likelihood of cable joint failure during a fire, the number of joints should be minimized during installation to ensure the circuit remains functional. If branch connections are necessary, the joints must be treated with appropriate fire-protection measure